NameLow Voltage Air Circuit Breaker Arc Chutes
CaptionAsbestos is suspected in the arc chutes of certain low voltage air circuit breakers. These include Nilsen type air circuit breakers (AB1, AB3, AB7 & NAB1) as well as GE OLD, GE NEW, GE MG14, MH CM22, WH CM2, SW LA50.
LocationIndustrial
SourceEssential Energy
Image Id236
Full Size
NameOil Circuit Breaker Closing Contactors
CaptionCover of an F250 closing contactor. The black backing board is also a suspected asbestos related material.
LocationCommercial
SourceEssential Energy
Image Id237
Full Size
NameOil Circuit Breaker Closing Contactors
CaptionThe second type of closing contactor that is present on F250, as well as J18/J22, is a similar type contactor with a variation in the arc shield only.
LocationIndustrial
SourceEssential Energy
Image Id238

Circuit Breaker Arc Chute Contractor Covers

Product description

Medium density asbestos cement sheet on a metal backing to protect protection relays against heat and electrical arcs from the contractors arc chute when operating.


These have been found in 11kV Westinghouse J18/B18 family of circuit breakers, in South Wales DX4 11kV breakers and in 33kV GCN breakers.33kV GCN approx. Pre 1965 breakers which have contractor covers that have a square box that is the same colour as the rest of the breakers. Ex-Electricity Commission breakers tend to have silver coloured boxes which do not contain asbestos.


Westinghouse Friable Risk - HIGH

Westinghouse Arc Chute Contactor covers are friable and can pose an immediate risk to employees if touched or disturbed. 


South Wales Non Friable Risk LOW

South Wales Arc Chute Contactor covers are considered to be bonded and work can occur in the vicinity of the contactor cover. 

Product type Electrical Insulation
Sub-Product type
Trading name(s) South Wales
Westinghouse
Other name(s) Arc Chute Covers, Closing Coil Contactor Covers
Build element
Product identification
These have been found in 11kV Westinghouse J18/B18 family of circuit breakers, in South Wales DX4 11kV breakers and in 33kV GCN breakers.33kV GCN approx. Pre 1965 breakers which have contractor covers that have a square box that is the same colour as the rest of the breakers. Ex-Electricity Commission breakers tend to have silver coloured boxes which do not contain asbestos.
Known uses
Asbestos fibre type
Friable or Non-Friable Friable
Known Supplier(s)
Known place of manufacture
Date / period of manufacture Pre 1987
Building construction period 1961-1970,1970-1980
Location Commercial
  • Electrical
Industrial
  • Electrical

 

More Images

Full Size
NameOil Circuit Breaker Closing Contactors
CaptionWhile not confirmed, asbestos is suspected in closing contactor enclosures of particular High Voltage Oil Circuit Breakers (HV OCB). These include Westinghouse GCN, J18, J22 and F250 type units. Closing contactors may be insulated by use of asbestos material in a cast iron enclosure.
LocationIndustrial
SourceEssential Energy
Image Id239
Full Size
NameWestinghouse B18 type switchgear
CaptionWestinghouse J18/b18 type 11kv circuit breakers - the flexible conduits (snakes) may contain asbestos that has the potential to migrate through the metal exterior.
LocationPlant
SourceEssential Energy
Image Id240

 